Tuesday, 19 January 2021

O Signal Received in AC Mode

Good day Pros!
Well, my heat pump turned into a block of ice and doesn't appear to be going into defrost.
Pulled out the garden hose and fully defrosted the coil.

York Affinity YZB04211A
YorkGuard VI board
Coil sensor: 62.5 kOhm (10°F)
Outdoor sensor: 47.4 kOhm (19°F)
Ambient: 21°F

Fault code is steady green, 4 red flashes. IOM states: O Signal Received in AC Mode.

I have recently noticed (maybe it's always done it) that the defrost shift seems to make an unholy screech.
Unit goes smoothly into A/C and Heating modes.

Jumping the Test pins doesn't force defrost.

I can't believe it's so difficult to find a qualified tech that can troubleshoot. Do I have the control board replaced?


source https://hvac-talk.com/vbb/showthread.php?2225840-O-Signal-Received-in-AC-Mode&goto=newpost

No comments:

Post a Comment