I have a variable speed blower + 41K BTU output on 1st stage furnace.
The blower is set to 1000 CFM for 1st stage. Altitude about 100ft.
1000 cfm x 43.3F temperature rise * 1.08 = 46,764 BTU
That's roughly 14% higher than the plate rating. Is that within the margin of error given the accuracy of the inputs? Or could something need adjustment?
The blower is set to 1000 CFM for 1st stage. Altitude about 100ft.
1000 cfm x 43.3F temperature rise * 1.08 = 46,764 BTU
That's roughly 14% higher than the plate rating. Is that within the margin of error given the accuracy of the inputs? Or could something need adjustment?