Have a 3 ton r407c air to water heat pump that occasionally throws a low pressure fault.
Of course it never does this when anyone is monitoring it, temperatures and pressures are perfectly normal during operation when anyone has looked at it.
Over time I noticed that it never occurs when ambient is under 40 degrees / 4 Celsius or over 54 degrees / 12 celcius.
I babysat it for a few hours when the temperature was due to plummet and finally caught it in action.
The low pressure occurs a few seconds after compressor shut off due to setpoint reached / start / end of defrost cycle.
Now since the fault occurs when the compressor isn't running I could set the carel controller to auto reset but I don't want to in case a genuine fault appears in the future.
The unit has copeland zh scroll, sporlan bbine-3-ga txv, plate heat exchanger, well sized receiver. All quality compoenents and works perfectly when the compressor is on.
Any ideas?
Of course it never does this when anyone is monitoring it, temperatures and pressures are perfectly normal during operation when anyone has looked at it.
Over time I noticed that it never occurs when ambient is under 40 degrees / 4 Celsius or over 54 degrees / 12 celcius.
I babysat it for a few hours when the temperature was due to plummet and finally caught it in action.
The low pressure occurs a few seconds after compressor shut off due to setpoint reached / start / end of defrost cycle.
Now since the fault occurs when the compressor isn't running I could set the carel controller to auto reset but I don't want to in case a genuine fault appears in the future.
The unit has copeland zh scroll, sporlan bbine-3-ga txv, plate heat exchanger, well sized receiver. All quality compoenents and works perfectly when the compressor is on.
Any ideas?