Concerned about deeper issues

Good morning HVAC community. I've got some deep concerns on my homes AC unit. Let me give you some details on what's cooking. New build home in Texas that's 5 years old. 2 carrier 16 SEER 3TON units. 1 for upstairs and one for downstairs. This June, the wife calls and the ac isn't working. When I get home I replace the run capacitor. All fixed for a month. Then the unit is running but the fan isn't spinning fast. Trouble shoot that a bad fan can kill the cap. So while replacing the fan I see that the contactor is cooked as well. it shows signs it was installed badly, only 1/2 of the copper threads actually were under the screw plate, and has begun to melt one of the poles so I replace it AND the fan motor.
Now tonight its very mild out and I hear the fan running but not the compressor. I check the thermostat and its set to auto and its under the run temp. Odd...so I click it to run and the compressor kicks on, cold air comes out. I click it to OFF and the compressor turns off but the fan on the unit stays on. Sounds like another run capacitor but its only been 4 months. Thoughts?